EasyManua.ls Logo

ComAp InteliDrive FLX LITE - Page 201

ComAp InteliDrive FLX LITE
228 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
ID-FLX Lite Global Guide
201
Related FW 2.5.0 Related applications
Comm object 25
Description
Output is active for 1 second after STOP SOLENOID (PAGE 200) activation. This signal is sent to ECU in case
of engine stop request.
Stop Pulse
6 back to List of LBO
Related FW 2.5.0 Related applications N/A
Comm object 1663
Description
Activation times prior to engine start:
If measured temperature is equal to PreheatTemp1 (°C) or lower, the LBO Preheat activates prior to
the engine start for time equal to value in setpoint PreheatTime1 (s)
If measured temperature is PreheatTemp2 C) or higher, the LBO Preheat activates prior to the
engine start for time equal to value in setpoint PreheatTime2 (s)
If the temperature is between the values, the LBO Preheat activates for time calculated by linear
approximation
The LBO Preheat is activated before engine start as same as Prestart (page 202) or Preglow (page
202), the time is defined by new setpoints (PreheatTime1/2, PreheatTemp1/2) described below.
Activation of Preheat (page 201) has a variable activation time based on the measured temperature
it can be activated either before or after Prestart LBO and is deactivated during cranking.
Input for temperature measurement is selected by setpoint PreheatSensor which is described
bellow
In case of invalid value on selected AIN, the LBO preheat will activate for time given by setpoint
PreheatTime2 = longest preheat time
Preheat
6 back to List of LBO
Related FW 2.5.0 Related applications
Comm object 37
Description
The output closes after reaching value of CrankRPM, fixed 30 RPM. The output opens after stopping of the
engine or in pause during repeated start.
Ignition
6 back to List of LBO

Table of Contents

Related product manuals