EasyManua.ls Logo

ComAp InteliDrive FLX LITE - Page 219

ComAp InteliDrive FLX LITE
228 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
ID-FLX Lite Global Guide
219
Related FW 2.5.0 Related applications
Comm object 436
Description
Output activates when Timer1 is active. Simultaneously the engine is started when is in AUT mode.
Timer1
6 back to List of LBO
Related FW 2.5.0 Related applications
Comm object 437
Description
Output activates when Timer2 is active. Simultaneously the engine is started when is in AUT mode.
Timer2
6 back to List of LBO
Related FW 2.5.0 Related applications
Comm object 1252
Description
The output closes prior to the engine start (Prestart) and opens when Starting RPM (page 114) speed is
reached. During repeated crank attempts the output is opened.
Glow plugs
6 back to List of LBO