EasyManua.ls Logo

ComAp InteliDrive FLX LITE - Page 220

ComAp InteliDrive FLX LITE
228 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
ID-FLX Lite Global Guide
220
Related FW 2.5.0 Related applications
Comm object 589
Description
Binary output function of Conveyor. See CONVEYOR (PAGE 194).
Conveyor
6 back to List of LBO
Related FW 2.5.0 Related applications
Comm object 590
Description
Binary output from Speed switch comparator see Group: Regulator on page 129.
SpeedSwitch
6 back to List of LBO
Related FW 2.5.0 Related applications
Comm object 591
Description
Binary output from Load switch comparator see Group: Load limit on page 135.
LoadSwitch
6 back to List of LBO
Related FW 2.5.0 Related applications
Comm object 265
Description
Output is controlled by panel 0/1 button when Panel Button (page 103) = Close Load, engine is running and
no Sd/Cd alarm is active. Close Load output is not closed in Idle and Cooling states and is disconnected
when any Sd/Cd alarm is activated.
Close Load
6 back to List of LBO
Related FW 2.5.0 Related applications
Comm object 756
Description
Output is controlled by panel 0/1 button when Panel Button (page 103) = Toggle. This setting changes the
Toggle output without any relation to Engine state or Alarm activity even if in OFF mode.
Toggle
6 back to List of LBO

Table of Contents

Related product manuals