InteliLite Global Guide
193
Subgroup: ECU Settings
Setpoint group Engine settings Related FW 1.2.1
Range [units] Primary / Secondary / Default [-]
Default value Default Alternative config NO
Step [-]
Comm object 10266 Related applications AMF, MRS
Config level Advanced
Setpoint visibility Visible only if ECU is configured
Description
This setpoint is used for choosing a frequency of ECU. Values are saved in ECU.
VOLVO EMSII (GE engines)
The nominal speed is selected via the VP Status proprietary frame, parameter "Frequency select".
SCANIA EMS/S6
The nominal speed is selected via parameters "Nominal speed switch 1" and "Nominal speed switch 2" in
the DLN1 proprietary frame.
Note: To lock this setpoint against editing you also have to lock setpoint ECU Frequency Select 1 (page
297) and ECU Frequency Select 2 (page 298).
ECU Frequency Select
6 back to List of setpoints
Setpoint group Engine settings Related FW 1.2.1
Range [units] 0 .. 100 [%]
Default value 50 % Alternative config NO
Step 1 %
Comm object 9948 Related applications AMF, MRS
Config level Advanced
Setpoint visibility Visible only if ECU is configured
Description
Enables to adjust engine speed in ECU via CAN bus. Nominal speed corresponds to 50%. This setpoint
should be used only for Volvo Penta and Scania engines. It has no effect on other engine brands.
Note: To lock this setpoint against editing you also have to lock setpoint ECU Speed Adjustment 1 (page
297) and ECU Speed Adjustment 2 (page 298).
ECU Speed Adjustment
6 back to List of setpoints