Setpoint group Generator settings Related FW 1.2.1
Range [units]
1 .. 200 [%] of Nominal Current (page 156)
Default value 50 % Alternative config NO
Step
1 % of Nominal Current (page 156)
Comm object 8284 Related applications AMF, MRS
Config level Advanced
Setpoint visibility Always
Description
Threshold for generator current asymmetry (unbalance). Protection is BOC (Breaker Open and genset
Cooldown).
Note: When there is no control of breakers, the type of protection is Sd not BOC.
Current Unbalance BOC
6 back to List of setpoints
Setpoint group Generator settings Related FW 1.2.1
Range [units] 0,0 .. 600,0 [s]
Default value 5,0 s Alternative config NO
Step 0,1 s
Comm object 8285 Related applications AMF, MRS
Config level Advanced
Setpoint visibility Always
Description
Delay for Current Unbalance BOC (page 197) protection.
Current Unbalance BOC Delay