InteliLite Global Guide
423
Value group Statistics Related FW 1.2.1
Units days
Comm object 14369 Related applications AMF, MRS
Description
Remaining hours of Rental Timer 2 (page 280).
Rental 2
6 back to List of values
Value group Statistics Related FW 1.2.1
Units hours
Comm object 8206 Related applications AMF, MRS
Description
Engine operation hours counter. The engine hours are incremented in the controller while the engine is
running.
Note: If an ECU is configured and it provides engine hours value, the value is taken from the ECU.
Running Hours
6 back to List of values
Value group Statistics Related FW 1.2.1
Units [-]
Comm object 11196 Related applications AMF, MRS
Description
Shutdown alarms counter. This counter counts all occurrences of a shutdown alarm, not only real shutdowns
of the gen-set, i.e. the counter is increased by 2 if two shutdown alarms appear simultaneously.
Shutdowns
6 back to List of values
Value group Statistics Related FW 1.2.1
Units days
Comm object 13770 Related applications AMF, MRS
Description
Assessment in days when the fuel tank will be empty.
Note: This value is based on setpoint Fuel Tank Volume (page 185) and value from ECU Fuel Rate. For
correct calculation of this value is necessary to have configured ECU which send Fuel Rate value,
otherwise this value can’t be calculated.
Time Till Empty
6 back to List of values

Table of Contents

Other manuals for ComAp InteliLite MRS16

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the ComAp InteliLite MRS16 and is the answer not in the manual?

ComAp InteliLite MRS16 Specifications

General IconGeneral
BrandComAp
ModelInteliLite MRS16
CategoryController
LanguageEnglish

Related product manuals