InteliLite Global Guide
467
Related FW 1.2.1 Related applications AMF, MRS
Comm object 1385
Description
The output is closed when there is the warning alarm from the analog input 4 of the controller present in the
alarmlist or isnt confirmed.
AL AIN 4 Wrn
6 back to Logical binary outputs alphabetically
Related FW 1.2.1 Related applications AMF, MRS
Comm object 1292
Description
This output is active when the Sd Battery Flat (page 584) or Wrn Battery Voltage (page 567) alarm is
present in the alarmlist or isn’t confirm.
AL Battery Flat
6 back to Logical binary outputs alphabetically
Related FW 1.2.1 Related applications AMF, MRS
Comm object 1272
Description
This output is active when the Battery Charge Fail (page 564) alarm is present in the alarmlist or isnt
confirmed.
AL Battery Charge
6 back to Logical binary outputs alphabetically
Related FW 1.2.1 Related applications AMF, MRS
Comm object 1293
Description
This output is active when the Wrn Battery Voltage (page 567) alarm is present in the alarmlist or isn’t
confirm.
AL Battery Voltage
6 back to Logical binary outputs alphabetically
Related FW 1.2.1 Related applications AMF, MRS
Comm object 9
Description
Output closes when any BOC alarm appears.
The output opens, if:
No BOC alarm is active and
Fault reset button is pressed
AL Common BOC
6 back to Logical binary outputs alphabetically