InteliLite Global Guide
567
Related applications AMF, MRS
Description
Alarm is active when there is start command and Rental Timer 1 (page 278) or
Rental Timer 2 (page 280) elapsed.
6 back to List of alarms level 1
Alarm Type Warning
Alarmlist message Wrn Battery Voltage
Alarm evaluated All the time
Related applications AMF, MRS
Description
This alarm informs the operator that the controller supply voltage is out of limits.
The following setpoints are related to it:
Battery < Voltage (page 190)
Battery > Voltage (page 190)
Battery <> Voltage Delay (page 190)
Wrn Battery Voltage
6 back to List of alarms level 1
Alarm Type Warning
Alarmlist message Wrn Charging Alternator Fail
Alarm evaluated Engine running only
Related applications AMF, MRS
Description
This alarm is issued if the engine is running and the voltage on the D+ terminal is
lower than 80% of the controller supply voltage. This alarm works similar to the red
“battery” alarm indicator on a vehicle dashboard.
The setpoint D+ Function (page 167) has to be in Charge Fail or Enabled position to
enable this alarm.
Wrn Charging Alternator Fail
6 back to List of alarms level 1
Alarm Type Warning
Alarmlist message Wrn Coolant Temperature Low
Alarm evaluated All the time
Related applications AMF, MRS
Description
This alarm indicates that the coolant temperature is lower than the temperature set
in Coolant Temperature Low Wrn (page 182) setpoint.
Wrn Coolant Temperature Low
6 back to List of alarms level 1
Alarm Type Warning
Alarmlist message Wrn Coolant Temp
Alarm evaluated All the time
Wrn Coolant Temp