InteliLite Global Guide
473
Related FW 1.2.1 Related applications AMF, MRS
Comm object 1419
Description
The output is closed when there is the shutdown alarm from the OIL PRESSURE (PAGE 546) in the alarmlist or
isn’t confirmed.
AL Oil Press Sd
6 back to Logical binary outputs alphabetically
Related FW 1.2.1 Related applications AMF, MRS
Comm object 1418
Description
The output is closed when there is the warning alarm from the OIL PRESSURE (PAGE 546) in the alarmlist or
isn’t confirmed.
Note: Binary output is also active if protection type is set to HistRecOnl and threshold level for history
record is reach.
AL Oil Press Wrn
6 back to Logical binary outputs alphabetically
Related FW 1.2.1 Related applications AMF, MRS
Comm object 109
Description
This output is active when the BOCOvercurrent IDMT (page 598) alarm is present in alarmlist or isn’t
confirm.
AL Overcurrent
6 back to Logical binary outputs alphabetically
Related FW 1.2.1 Related applications AMF, MRS
Comm object 1268
Description
This output is active when the Sd Overload (page 592) alarm is present in the alarmlist or isn’t confirm.
AL Overload BOC
6 back to Logical binary outputs alphabetically
Related FW 1.2.1 Related applications AMF, MRS
Comm object 1269
Description
This output is active when the Wrn Overload (page 575) alarm is present in alarmlist or isn’t confirm.
AL Overload Wrn
6 back to Logical binary outputs alphabetically