InteliLite Global Guide
592
6 back to List of alarms level 2
Alarm Type Shutdown
Alarmlist message Sd Overload
Alarm evaluated All the time
Related applications AMF, MRS
Description
The alarm is issued when the gen-set power is over the limit for time period longer
than the delay. The behavior of the overload alarm is adjusted by the following
setpoints:
Overload BOC (page 194) adjusts the overload limit.
Overload BOC Delay (page 194) adjusts the delay
Sd Overload
6 back to List of alarms level 2
Alarm Type Shutdown
Alarmlist message Sd Overspeed
Alarm evaluated All the time
Related applications AMF, MRS
Description
This alarm occurs immediately when the engine speed has exceeded the limit. The
behavior of the overspeed alarm is adjusted by the following setpoints:
Overspeed Sd (page 175) adjust the overspeed limit
Overspeed Overshot (page 176) adjust the additional overspeed limit
Overspeed Overshot Period (page 176) adjust the time period of additional
overspeed limit
Sd Overspeed
6 back to List of alarms level 2
Alarm Type Shutdown
Alarmlist message Sd RPM Measurement Fail
Alarm evaluated During cranking
Related applications AMF, MRS
Description
The alarm is issued if the engine speed has not exceeded the Starting RPM (page
166) within the Maximum Cranking Time (page 165), although some of additional
running engine indication sources indicate that the engine has started.
Sd RPM Measurement Fail
6 back to List of alarms level 2
Alarm Type Shutdown
Alarmlist message Sd Short Circuit
Alarm evaluated All the time
Sd Short Circuit