InteliLite Global Guide
593
Related applications AMF, MRS
Description
This is a fast overcurrent protection. The following setpoints are related to this
alarm:
Short Circuit BOC (page 195) adjusts the short current limit
Short Circuit BOC Delay (page 195) adjusts the delay in fine steps
6 back to List of alarms level 2
Alarm Type Shutdown
Alarmlist message Sd Start Fail
Alarm evaluated When the gen-set is being started
Related applications AMF, MRS
Description
This alarm will be issued after all attempts to start the gen-set have run out but the
gen-set did not start. The following setpoints are related to this alarm:
Cranking Attempts (page 165) adjust the number of attempts
Sd Start Fail
6 back to List of alarms level 2
Alarm Type Shutdown
Alarmlist message Sd Underspeed
Alarm evaluated Engine running only
Related applications AMF, MRS
Description
This alarm will be issued when the gen-set is running and then stops by itself, i.e.
the RPM drops under the value of setpoint Starting RPM (page 166).
The underspeed alarm starts to be evaluated after successful gen-set start and is
being evaluated for the entire time that the fuel solenoid is on.
Sd Underspeed
6 back to List of alarms level 2
Other type
Alarm Type BOC
Alarmlist message BOC Coolant Temperature
Alarm evaluated All the time
Related applications AMF, MRS
Description
This alarm indicates that the coolant temperature is higher than the temperature set
in Coolant Temperature Sd (page 179) setpoint.
BOC Coolant Temp
6 back to List of alarms level 2