EasyManuals Logo

ComAp InteliLite MRS16 User Manual

ComAp InteliLite MRS16
632 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #594 background imageLoading...
Page #594 background image
InteliLite Global Guide
594
Alarm Type BOC
Alarmlist message BOC Current Unbalance
Alarm evaluated All the time
Related applications AMF, MRS
Description
This alarm evaluates the unbalance of the phase currents, i.e. the difference
between highest and lowest phase current at any given time. The following
setpoints are related to it:
Current Unbalance BOC (page 197) adjusts the maximum allowed difference
between the highest and lowest phase current at any given time.
Current Unbalance BOC Delay (page 197) adjusts the alarm delay.
BOC Current Unbalance
6 back to List of alarms level 2
Alarm Type BOC
Alarmlist message BOC Fence 1 Alarm
Alarm evaluated All the time
Related applications AMF, MRS
Description
This alarm evaluates the GPSposition of gen-set. The following setpoint are
related to it:
Geo-Fencing (page 285)
Fence 1 Protection (page 286)
Fence Radius 1 (page 284)
BOC Fence 1 Alarm
6 back to List of alarms level 2
Alarm Type BOC
Alarmlist message BOC Fence 2 Alarm
Alarm evaluated All the time
Related applications AMF, MRS
Description
This alarm evaluates the GPSposition of gen-set. The following setpoint are
related to it:
Geo-Fencing (page 285)
Fence 1 Protection (page 286)
Fence Radius 1 (page 284)
BOC Fence 2 Alarm
6 back to List of alarms level 2

Table of Contents

Other manuals for ComAp InteliLite MRS16

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the ComAp InteliLite MRS16 and is the answer not in the manual?

ComAp InteliLite MRS16 Specifications

General IconGeneral
BrandComAp
ModelInteliLite MRS16
CategoryController
LanguageEnglish

Related product manuals