InteliLite Global Guide
595
Alarm Type BOC
Alarmlist message BOC Fuel Level
Alarm evaluated All the time
Related applications AMF, MRS
Description
This alarm indicates that the fuel level is lower than the level set level in Fuel Level
Sd (page 183) setpoint.
BOC Fuel Level
6 back to List of alarms level 2
Alarm Type BOC
Alarmlist message BOC + Name of analog input
Alarm evaluated All the time
Related applications AMF, MRS
Description
This alarm indicates that the value of general analog protection is out of BOC
protection limit.
BOC AIN Prot
6 back to List of alarms level 2
Alarm Type BOC
Alarmlist message BOC + Name of binary input
Alarm evaluated All the time
Related applications AMF, MRS
Description
Binary input also can be adjusted like alarm. In this case message in alarmlist
contains prefix - BOC and binary input name. This alarm occurs, when appropriate
binary input is active.
BOC BIN Protection 1..48
6 back to List of alarms level 2
Alarm Type BOC
Alarmlist message BOC Generator L1 < Voltage
Alarm evaluated Generator excited only
Related applications AMF, MRS
Description
This alarm evaluates the generator phase voltage in phases 1. The following
setpoints are related to it:
Generator < Voltage BOC (page 199)
Generator <> Voltage Delay (page 200)
BOC Generator L1 < Voltage
6 back to List of alarms level 2

Table of Contents

Other manuals for ComAp InteliLite MRS16

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the ComAp InteliLite MRS16 and is the answer not in the manual?

ComAp InteliLite MRS16 Specifications

General IconGeneral
BrandComAp
ModelInteliLite MRS16
CategoryController
LanguageEnglish

Related product manuals