EasyManuals Logo

ComAp InteliLite MRS16 User Manual

ComAp InteliLite MRS16
632 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #500 background imageLoading...
Page #500 background image
InteliLite Global Guide
500
Related FW 1.2.1 Related applications AMF, MRS
Comm object 77
Description
This output is active when the generator voltage and frequency is within limits. It is deactivated:
immediately when the voltage/frequency gets out of limits (when GCB is not closed)
or
with an appropriate delay after the voltage/frequency has got out of limits (when GCB is closed)
The limits for under/overvoltage, under/overfrequency and voltage unbalance as well as appropriate delays
can be found in the setpoints Group: Generator settings (page 194).
Generator Healthy
6 back to Logical binary outputs alphabetically
Related FW 1.2.1 Related applications AMF, MRS
Comm object 1252
Description
This output is dedicated for diesel engine only. This output will close for exact time pre-set by setpoint Glow
Plugs Time (page 168) before every starting attempt. The output opens in same time as the STARTER (PAGE
510) output closes (100 ms after PRESTART (PAGE 506) output opens).
Image 8.173 Glow Plugs
Glow Plugs

Table of Contents

Other manuals for ComAp InteliLite MRS16

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the ComAp InteliLite MRS16 and is the answer not in the manual?

ComAp InteliLite MRS16 Specifications

General IconGeneral
BrandComAp
ModelInteliLite MRS16
CategoryController
LanguageEnglish

Related product manuals