InteliLite Global Guide
621
LED Description State State
TxUSB No data are received on USB Dark
Data are received on USB Blink
RxUSB No data are transmitted on USB Dark
Data are transmitted on USB Blink
PWR No power supply Dark
Power supply OK Continuous light
RUN When at least one controller is active on the CAN bus Continuous light
After connection power supply - no controller detected on the CAN
bus (during communication speed detection).
Blink
Wiring
I-LB+ has to be connected to modem via standard modem cable (full RS232) where the DSR (Data Set Ready)
signal detects modem presence (when MODEM (HW) type selected). Three-wire RS232 cable (TxD, RxD,
GND) can be used (e.g. for GSM modems) when MODEM (SW) type is selected.
Technical data
Power supply 8 to 36 V DC
Current consumption 100 mA at 24 V
Interface to controller CAN2
Interface to modem or PC RS232, RS485, USB
Storage temperature - 40 °C to + 80 °C
Operating temperature - 30 °C to + 70 °C
Dimensions (WxHxD) 95x96x43 mm (3,7”x3,8”x1,7”)
General data
Extension modules
Inteli AIN8 621
Inteli IO8/8 626
Inteli AIN8
Inteli AIN8 module is extension module equipped with analog inputs. Inteli AIN8 module is connected to
controller by CAN1 bus.