InteliPro, SW version 1.0, ©ComAp – May 2011
InteliPro Reference Guide
4-17
MODEM: Analog or GSM modem
MODBUS : InteliPro Modbus protocol
Default setting: DIRECT
Note:
For a module, providing 2 communication channels, this switch defines the communication on the first
channel (RS232 in case of IL-NT RS232-485).
COM2 Mode [ DIRECT / MODEM / MODBUS ]
Switch, defining what protocol/mode of communication is used on the seconf communication channel
of a plug-in communication module.
DIRECT: InteliPro (LiteEdit) communication protocol
MODEM: Analog or GSM modem
MODBUS : InteliPro Modbus protocol
Default setting: DIRECT
Note:
For a module, providing 2 communication channels, this switch defines the communication on the
second channel (RS485 in case of IL-NT RS232-485).
ModemIniString
Auxiliary modem initialization string – executed after the default modem initialization string in case of
modem communication.
ModbusComSpeed [ 9600 / 19200 / 38400 / 57600 bps ]
Adjusting of the speed of Modbus communication
Default setting: 9600 bps
CAN Bus Mode [ 32C / 8C ]
CAN bus speed selection. Use this setpoint in case that you operate InteliPro together with other
ComAp contollers connected via CAN bus.
32C: High speed CAN (250 kbps) applicable up to 32 controllers, CAN bus length limited up
to 200 meters.
8C: Low speed CAN (50 kbps) applicable up to 8 controllers, CAN bus length limited up to
900 meters.
Default setting: 32C
IBLite IP Addr
IP address of IB-Lite module
IBLite NetMask
IB-Lite network mask
IBLite GateIP
IP address of gateway for IB-Lite
IBLite DHCP
automatic IP address assignment through DHCP server
IP Addr Mode
FIXED or AUTOMATIC mode of IP address assignment
ComAp Port
Port for ComAp communication over IB-Lite or IL-NT-GPRS module