InteliPro, SW version 1.0, ©ComAp – May 2011
InteliPro Reference Guide
4-20
ALWAYS: protection is enabled all the time except when blocked by the assigned blocking
input. The ALWAYS option is not dependent on CB1 Feedback or CB2 Feedback
binary inputs.
Default setting: ALLWAYS
ShTermPar Prot [ENABLED / DISABLED]
Enabling the protection for maximum time of short parallel operation.The protection trips after
MaxParallTime from activation of both CB1 Feedback abd CB2 Feedback inputs.
DISABLED: short term parallel protection is disabled
ENABLED: short term parallel protection is enabled
Default setting: DISABLED
Prio Switching [ DISABLED / CB1 -> CB2 / CB1 <- CB2 / CB1 <-> CB2 ]
Setpoint indicates the method for "priority switching":
DISABLED: no method of priority switching is applied
CB1 -> CB2: CB1 is considered as the primary switch. If the feedback doesn't come in preset
period, Bak Trp 1 is issued and at the same time Trp 2 is issued.
CB1 <- CB2: CB2 is considered as the primary switch. If the feedback doesn't come in preset
period, Bak Trp 2 is issued and at the same time Trp 1 is issued
CB1 <-> CB2: both CBs provide a backup switching for one another. If the CB1 feedback doesn't
come in preset period, Bak Trp 1 is issued and at the same time Trp 2 is issued, if
the CB2 feedback doesn't come in preset period, Bak Trp 2 is issued and at the
same time Trp 1 is issued.
Default setting: DISABLED
IPro-SW Key
Software key unlocking the requested optional SW functions of InteliPro.
Default setting: empty
Note:
This setpoint is not overwritten after FW upgrade. The setpoint is not visible on InteliPro display in
reading mode to avoid confusion of the user. It is possible to edit this setpoint through InteliPro display
and pushbuttons - in this mode it becomes visible. It is however advisable to use LiteEdit for filling-in
the SW Key.
Aux V<>
Aux >V [ V ]
Warning level for battery overvoltage.
Step: 0.1 V
Range: Aux <V – 40 V
Default setting: 36 V
Aux <V [ V ]
Warning level for low battery voltage.
Step: 0,1 V
Range: 8 – Aux >V V
Default setting: 18 V
Aux V Del [ s ]
Delay for battery voltage warnings.
Step: 1 s
Range: 0 - 600 s
Default setting: 5 s

Table of Contents

Other manuals for ComAp InteliPro

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the ComAp InteliPro and is the answer not in the manual?

ComAp InteliPro Specifications

General IconGeneral
BrandComAp
ModelInteliPro
CategoryRelays
LanguageEnglish

Related product manuals