EasyManua.ls Logo

Comelit 41CPE118 - Page 38

Comelit 41CPE118
94 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
17/06/2020 14:06
41IOM022
Address
Loop Number
Device Zone
3
2
1
EnabledNewDevice State
More
Remove
OFF
Name
Save
17/06/2020 14:06
InputChannel 1
Name
InputChannel 2
Name
OutputChannel 3
Name
OutputChannel 4
Name
To enter the input or output activation type, press the button alongside the Channel with the corresponding number and select
one of the options. A name of up to 40 characters can be assigned to each channel in the editable bar next to the “Name”
label”.
INPUT CHANNEL rapid programming:
Input: no “rapid activation” is associated with the input and it can be used in fire panel programming logics (virtual inputs /
outputs);
Alarm*: if activated, the module functions as a fire detector and generates a “FIRE ALARM” event to the panel;
Evacuate*: if activated, it generates an “EVACUATE” event to the panel;
GAS Alarm: if activated, the module generates an indication (Gas alarm) on the panel display, useful for interfacing
between conventional gas detectors;
Technical Alarm: if activated, the module generates an indication (Technical alarm warning) on the panel display.
* Does not conform to EN54-2
OUTPUT CHANNEL rapid programming:
Output: no “rapid activation” is associated with the output and it can be used in fire panel programming logics (virtual
inputs / outputs);
Alarm: if a Common fire alarm event occurs the output is enabled.
Evacuate: if an Evacuate alarm event occurs the output is enabled.
Reset: in the event of a Reset action the output is enabled for a pre-set time.
Sounders Mode: if a Loop sounder activation event occurs the output is enabled.
To save any new parameters, press “Save” on the main device screen.
38

Table of Contents