7. Appendices
Appendix A: Error messages shown on the 41CPE118 fire alarm panel display:
Message text Description
Alarm Common Fire Alarm
Loop Device Type Error A dierent type of device than the specified type has been found at the address.
Loop Device Fault The device is not responding (removed or faulty).
Double Address Devices with the same address are present on the Loop.
PreAlarm Fire alarm originating from a sensor/button for a zone set as “2 Devices” or “Double
alarm”.
Evacuate Manual button activated, or the “Evacuate” panel button.
Loop Device Input Fault Fault at the input of a Loop device.
Loop Device Output Fault Fault at the output of a Loop device.
Loop Device Sounder-Fault Sounder on Loop faulty (short-circuit or line opened).
Fault Output - Fault Fault at the panel fault output (short-circuit or line opened).
Fire Brigade - Fault Fault at the panel Fire Brigade output (short-circuit or line opened).
Fire Protection - Fault Fault at the panel Fire Protection output (short-circuit or line opened).
Loop Device Disabled A Loop device has been disabled.
Chamber Fault Sensor chamber photodiode fault.
Clean Me Now Photodiode inside the sensor chamber dirty.
TEST ALARM Alarm originating from a sensor for a zone in Test mode.
Signal Blockage Signal inhibited at the linear barrier.
Hi Signal Signal too high from the linear barrier.
Drift Alert Balancing threshold reached in the sensor.
Earth Fault Dispersion to earth < 10k.
Battery Low Panel battery low.
Charger Fault Fault in the battery recharging circuit.
Battery Loss Panel battery loss.
AC Loss 230 V main power supply loss.
Sounder Fault Fault at the panel sounder output (short-circuit or line opened).
AUX 24V Fault Short-circuit (no power) at the AUX 24V output.
AUX 12V Fault Short-circuit (no power).
Periphery Device Fault A periphery device is not responding (removed or faulty).
Periphery Device Type Error A dierent type of device than the specified type has been found at the address.
External Power Supply Fault Problem with the external power supply (battery low, battery loss, charger fault,
main power supply loss or dispersion to earth).
External Power Supply Loss There is an external power supply loss.
Zone Disabled The zone is disabled.
Zone In Test The zone is in test mode.
Sounder Disabled The Sounder output has been disabled.
Fire Brigade Output Disabled The Fire Brigade output has been disabled.
Fire Protection Output Disabled The Fire Protection output has been disabled.
Fault Output Disabled The Fault output has been disabled.
Reset The control panel has been reset.
Silence Alarm The sounders have been silenced.
Ram Error Error in RAM.
Flash Error Error in permanent storage.
Panel Fault Connection with the other panel interrupted (when two or more panels are
connected in a network).
Double IP address Panel IP address duplicated.
Double Panel number Panel number duplicated (when two or more panels are connected in a network).
88