Message text Description
Double IP address and Panel number Panel IP address and number duplicated (when two or more panels are connected
in a network).
New Periphery Devices Found The panel has recognised new periphery devices in the panel configuration.
New Loop Devices Found New devices have been recognised on the Loop.
Loop Short Short-circuit in the Loop.
Loop Break Loop interrupted.
Loop Zero Address One or more unaddressed devices is/are present on the Loop.
Activated output Output enabled.
Network Fault Fault in the RS485 network or the LAN.
Wrong Error Code Unknown fault message code.
Alarm Output Alarm or alarm event from an output.
Earth Fault function DISABLED The earth fault indication has been disabled from the panel menu.
Transmitting device active The Fire Brigade output has been enabled.
Extinguishing output active The Fire Protection output has been enabled.
Sirens active The Sounder output has been enabled.
User log o Logout from the “User” programming level.
Installer log o Logout from the “Installer” programming level.
User log on Login at “User” programming level.
Installer log on Login at “Installer” programming level.
GAS ALARM ! Gas alarm from device 41IOM010.
WARNING! Technical warning from device 41IOM010.
Battery High Resistance High (Ri>0.3 Ω) resistance value inside the battery. The battery should be replaced
with a new one immediately!
High Resistance Disabled The high resistance inside battery indication has been disabled from the panel
menu.
Internal Buzzer Disabled The internal buzzer has been disabled from the panel menu.