Return the Control to Service
After the required work is completed, disconnect the
control from the test set and follow this procedure to return
the control to service:
1. While still in service shop, appropriate personnel must
verify that all control settings are correct.
2. Reconnect the ground cable to the control.
3. Control cable properly connected and supported.
4. Plug in the control battery.
Note: The Form 6 pole-mount recloser control will not
power up until AC power is applied.
5. Verify the selector switch on the Power Supply/Battery
Charger Board is set to the correct position based
upon the incoming power supply:
• For 120 VAC incoming power, the selector switch
must be set to the 115V position.
• For 240 VAC incoming power, the selector switch
must be set to the 230V position.
6. Apply AC power to the control.
7. Disable GND TRIP BLOCKED.
A. Press the CHANGE button on the Operator Panel to
enter the CHANGE mode.
B. Depress the GND TRIP BLOCKED button within ten
seconds after entering the CHANGE mode.
Note: Once selected (or after ten seconds), the control
returns to normal operation.
8. Verify the control clock is set to the current time after
AC power has been reapplied.
Note: The control clock may require resetting if the operating
power has been disconnected for more than thirty
days. Refer to Service Information S280-70-4
(ProView 4.X.X) or S280-70-21 (ProView 5.X.X) Form
6 Microprocessor-Based Recloser Control
Programming Guide for information on setting the
control clock.
RECLOSER VTC INTERFACE
Control-Powered Type NOVA reclosers with serial numbers
100,000 and above, as listed in Table 15, require a VTC-
ready control. They are equipped with a 19-pin control
cable receptacle and can be identified by labels prominently
displayed on the bottom of the recloser tank and on the
side near the 19-pin receptacle, as shown in Figure 50
below.
For more information on the Control-Powered NOVA
Interface, refer to Service Information S280-42-1.
Form 6 Microprocessor-Based Pole-mount Recloser Control Installation and Operation Instructions
52
CAUTION: Equipment misoperation. Verify that
the 120/240 VAC selector switch is correctly set
for incoming voltage. Failure to comply may cause
misoperation (unintentional operation) of the control
and/or equipment damage resulting in personal injury.
T278.0
CAUTION: Equipment misoperation. Do not
connect this control to an energized recloser until
all control settings have been properly programmed and
verified. Refer to the programming information for this
control. Failure to comply can result in control and
recloser misoperation, equipment damage, and personal
injury. G110.3
CAUTION: Equipment misoperation. The control-
powered NOVA reclosers that require a VTC
interface must be used with VTC-ready controls. Failure
to use a VTC-ready control will result in failure to trip or
close. G144.0
Figure 50.
Receptacle side view and bottom view of NOVA
recloser tank, showing placement of VTC label.
TABLE 15
Serial Number Break for Control-Powered NOVA Reclosers
with VTC
Control-Powered NOVA Serial No.
NOVA15 100,000
NOVA27 100,000
NOVA38 100,000
Note: Control-powered NOVA reclosers with serial numbers
below those listed in Table 15 do not require a VTC-
ready control. Refer to the recloser nameplate for the
serial number.