LEMCOM CANopen® – User manual Detailed description of CANopen objects
COVAL – LMCOP-EN-A-1155UM0068 34/49
12.14 2017h – Communication fault counter (local bus)
The number of communication faults on the local bus (master/secondary CAN bus) can be accessed
using the following SDO command:
Client (master) server (LEMCOM)
The subindex is used to define the module to query (from 1 to 16):
- Subindex = 0x01 request for counter value on master module (address #0)
- …
- Subindex = 0x10 request for counter value on secondary module at address #15
The reply is as follows:
Server (LEMCOM) Client (master)
The number of faults is provided in hexadecimal format by the following:
Byte 3 – Byte 2 – Byte 1 – Byte 0
12.15 2018h – Communication fault counter (client bus)
The number of communication faults on the client CAN bus (CANopen communication between the
PLC and the LEMCOM master module) can be accessed using the following SDO command:
Client (master) server (LEMCOM)
The subindex is used to define the module to query (from 1 to 16):
- Subindex = 0x01 request for counter value on master module (address #0)
- …
- Subindex = 0x10 request for counter value on secondary module at address #15
The reply is as follows:
Server (LEMCOM) Client (master)
The number of faults is provided in hexadecimal format by the following:
Byte 3 – Byte 2 – Byte 1 – Byte 0