COMPRESSOR WILL NOT START
Defective
starting
component
(capacitor,
relay).
Close Service Door.
Check Harness from Compressor
to AC Distribution Box.
Compressor
will not start.
Service Door is
open.
Compressor is
unplugged.
Replace Service Door Switch.
Defective Door
Switch.
Check power source at outlet.
Replace Encapsulated
Temp. Sensor.
Low voltage.
Defective
Encapsulated
Temp. Sensor.
In Relay Toggle, test that the
Compressor will turn on.
Test in
Programming
Service Mode.
Replace starting
component.
Defective
Compressor.
Defective
Environmental
Board in AC
Distribution Box.
Replace Compressor.
Replace Environmental
Control Board.