MACHINE NOT COOLING
Condenser Fan
or Evaporator
Fan not
running.
Evaporator is
iced up.
Clean Condenser.
Replace Encapsulated Temp. Sensor.
Machine not
cooling.
Dirty or
clogged
Condenser.
Clear Rear Screen of obstructions.
Ensure rear of Cabinet is at least
4” (10cm) from wall.
Defective
Encapsulated
Temp. Sensor.
Move Machine.
Machine in
direct sunlight
or near a heat
source.
Replace faulty seal(s).
Restricted
airflow.
Check Fan Blades for obstruction. Check
Fan circuit. Replace as necessary.
Check for air leaks or clogged
Condensate Drain.
Move Machine.
Machine in
location with
humidity above
70%.
Faulty Product
area seal(s).