EasyManua.ls Logo

Daikin FT25DVM - Freeze-Up Protection Control

Daikin FT25DVM
268 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Functions of FT25/35/50D, FT09/13/15D Models Si01-501
28 Defails of Functions
1.7 Freeze-up Protection Control
When the indoor heat exchanger temperature falls below 3°C in cooling or in dry operation,
the compressor and the outdoor fan are forced to turn OFF.
the indoor fan rotates at the L tap (in cooling operation) or LL tap (in dry operation).
Note that this function is not activated for 6 minutes after compressor turns ON.
When the indoor heat exchanger reaches 13 °C, the compressor and the outdoor fan restart the
operations.
Indoor heat exchanger
temperature
13˚C
3˚C
Stop
Return
(R4833)

Table of Contents

Related product manuals