Si01-501 Functions of FT60D Model
Defails of Functions 37
2.7 POWERFUL Operation
Outline In order to exploit the cooling capacity to full extent, operate the air conditioner by increasing the
indoor fan rotating speed and the compressor frequency.
Details of the
Control
When Powerful button is pushed in each operation mode, the fan speed/setting temperature will
be converted to the following states in a period of twenty minutes.
Ex.) : Powerful operation in cooling mode.
Operation mode Fan speed Target set temperature
Cooling H tap + 90 rpm 18°C
Dry Dry rotating speed +
50 rpm
Normally targeted
temperature in dry
operation; Approx. –2°C
Fan H tap + 90 rpm —
(R4834)
Target temp.
Fan
90rpm
Set temp.
18˚C
Powerful ON
Powerful OFF
H tap
Set tap
It should be the lower limit of cooling temperature.
It counts 20 min. also in the remote controller.
Ending condition: "or" in 1 to 3
1. After the lapse of 20 minutes.
2. Stop
3. Powerful operation is OFF.
20min.