Si18-201 Method of Field Set
Operating Test 215
3. When installing Sky Air simultaneous operation multi-unit, set to either twin or triple.
Only when the factory setting is changed, it is necessary to make a setting using a remote
controller.
4. For further details, see the installation instruction.
5. Since drafts may result, carefully select the installation location.
6. When power returns, units resume the settings made before the power outage.
Caution When auto restart after power outage reset is set, be sure to turn off air conditioners, then cut
off the power supply before conducting maintenance, inspection and other work. If the power
supply is cut off with the power switch left ON, air conditioners will automatically start operating
when the power supply is turned on.
7. Do not set any items other than those listed in the above table.
8. Functions that indoor units are not equipped with will not be displayed.
9. When returning to normal mode, 88 may be displayed on the LCD section of the remote
controller due to initialization operation.
2.1.3 Detailed Explanation of Setting Modes
Ceiling Type Setting Switch for Air Flow Adjustment
Make the following setting according to the ceiling height. The setting position No. is set to 01
at the factory.
"
In the Case of FHYC (35 to 71 class)
Air Flow Direction Setting
Set the air flow direction of indoor units as given in the table below. (Set when optional air outlet
blocking pad has been installed.) The second code No. is factory set to 01.
Setting Table
Filter Sign Setting
If switching the filter sign ON time, set as given in the table below.
Set Time
*FH(Y)C and FH(Y) only are 1,250 hrs.
No. of Air Outlets Used
4-way Outlets 3-way Outlets 2-way Outlets
Ceiling
Height
Standard (N) Lower than 2.7 m Lower than 3.0 m Lower than 3.5 m
High Ceiling &
(H)
Lower than 3.0 m Lower than 3.3 m Lower than 3.8 m
Higher Ceiling '
(S)
Lower than 3.5 m Lower than 3.5 m
Mode No. First Code No. Second Code
No.
Setting
13 (23) 1 01 F : 4-direction air flow
02 T : 3-direction air flow
03 W : 2-direction air flow
Filter Specs.
Setting
Long Life Standard Ultra Long Life Filter
Contamination Light 2,500 hrs. 200 hrs. 10,000 hrs.
Contamination Heavy 1,100 hrs. * 100 hrs. 5,000 hrs.