Si18-201 Method of Field Set
Operating Test 223
2.4 Precautions: For RMK140J / RMX140J Outdoor Unit
Users
Applicable model series
Outside air temperature for operation
These cases are not troubles
* If you use the indoor unit listed below, and have it connected to the multi-type outdoor unit
(RMK140J/RMX140J), be sure to read this precautions.
* Use the furnished remote controller.
For the ceiling-mounted cassette type, the remote controller is an option.
Choose one of the following remote controllers.
(1) Wired type: BRC1B61 (C) (2) Wireless type: BRC7C612W (C) (H/P)
BRC7C613W (C) (C/O)
Outdoor Unit
Heat Pump
RMX140J
Cooling only
RMK140J
FHYC35/50/60/71KV1C, FHYC35/50/60/71KVE
FDYM60/03FV1, FDYM60/03FV1C, FDYM60/03FVAL
FTK25/35J
FTK50/60H
CDK25/35/50/60HA
FLK25/35/50/60H
FTX25/35J
FTX50/60H
CDX25/35/50/60HA (J)
FLX25/35/50/60H
-15 ~ 15.5 ˚CWB
-5 ~ 46 ˚CDB
Heat pump
5 ~ 46 ˚CDB
Cooling only
Heating Operation
Cooling Operation
Package
Air Conditioner
Room
Air Conditioner
Ceiling-Mounted Cassette Type
Wall-Mounted Type
Duct-Connected Type
Ceiling-Mounted Duct Type
Floor/Ceiling-suspended Dual Type
Indoor
Unit
(1) All indoor units
In heating operation, when all indoor units are stopped, the outdoor unit stops its operation
automatically after 5 minutes. This is a part of preparation process for the next operation, not a failure.
With the thermostat OFF (*1), the fan may start/stop automatically; this is not a failure.
In heating operation, no warm air may come out temporarily. This is to protect the outdoor unit,
not a failure. At this point, "DEFROST" is displayed on the wired-type remote controller.
With the thermostat OFF (*1), the fan may start/stop automatically; this is not a failure.
At this point, "DEFROST" is displayed on the wired-type remote controller.
(*1) Thermostat OFF: After the room temperature reaches the set temperature,
indoor units enter the operation stand-by state.
In heating operation, fan operation cannot be performed.
If the fan operation is selected, the remote controller will display it as a current mode.
However, the fan operation will not be performed.
In simultaneous operation in two or more rooms, when heating operation is performed in one room,
cooling operation cannot be performed in other rooms. The mode in the room where operation
began first is given priority.
(2) Floor/ceiling-suspended dual type units
(3) Skyair indoor units
2P042644-17G

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Daikin FTK35JAVET and is the answer not in the manual?

Daikin FTK35JAVET Specifications

General IconGeneral
BrandDaikin
ModelFTK35JAVET
CategoryHeat Pump
LanguageEnglish

Related product manuals