EasyManuals Logo

Daikin FTK35JAVET User Manual

Daikin FTK35JAVET
410 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #266 background imageLoading...
Page #266 background image
Si18-201 Troubleshooting - SkyAir Indoor Unit
Service Diagnosis 253
2.6.2 Malfunction of Drain Water Level System (Float Type)
Remote
Controller
Display
A3
Applicable
Models
FHYC
Method of
Malfunction
Detection
By float switch OFF detection
Malfunction
Decision
Conditions
When rise of water level is not a condition and the float switch goes OFF.
Supposed
Causes
"
Failure of drain pump
"
Improper drain piping work
"
Drain piping clogging
"
Failure of float switch
"
Failure of indoor unit PC board
"
Failure of short-circuit connector

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Daikin FTK35JAVET and is the answer not in the manual?

Daikin FTK35JAVET Specifications

General IconGeneral
BrandDaikin
ModelFTK35JAVET
CategoryHeat Pump
LanguageEnglish

Related product manuals