Si18-201 Wiring
Caution Before Operation 349
2. BP unit connection priority
When connecting to the BP unit, always start the connection with BP1 of the terminal board (at outdoor unit side) in
the sequential order.
Improper connection will cause a transmission failure, preventing the operation.
123 123
123 123
123 123 123
123
123 123
123
123 123
123
123 123 123 123
123
123 123
123 123
TO BP1
OUTDOOR UNIT
TO BP2 TO BP3 TO BP1 TO BP2 TO BP3
TO BP1 TO BP2 TO BP3
TO BP1 TO BP2 TO BP3
TO BP1 TO BP2 TO BP3
OUTDOOR UNIT OUTDOOR UNIT
OUTDOOR UNIT OUTDOOR UNIT
BP UnitBP Unit
BP Unit
BP Unit BP Unit BP Unit
BP Unit BP Unit
Make sure numbers
1, 2, and 3 all match.
1
2
3
123 LN
BP
unit
Safety
breaker
Earth leakage
circuit breaker
Earth
When wire length exceeds
10 m, use 2.0-mm wires.
H05VV
H05VV
2.6mm
(5.5mm
2)
1.6mm
or
2.0mm
Firmly fix the wires with
the terminal screws.
Outdoor unit
Power
supply
Firmly fix the wires with
the terminal screws.
Be sure to attach this.