General Functionality ESIE02–01
2–6 Part 2 – Functional Description
3
1
2
4
5
3 Outdoor
heat
exchanger
R2T Cooling Optimise discharge temp. (cond. temp.)
Integral capacity calculation (to determine
freeze-up)
Heat-
ing
Optimise discharge temp. (evap. temp.)
Defrost start/stop
4 Outdoor
air return
R1T Cooling
Outdoor fan speed control
Start-up control expansion valve and outdoor
unit fan
Integral capacity calculation (to determine
freeze-up)
Heat-
ing
Integral capacity calculation (to determine
defrost)
Start-up control expansion valve and outdoor
unit fan
5Discharge
pipe com-
pressor
R3T Cooling
Cooling overload
Check refrigerant shortage/too much refrigerant
Expansion valve control
Heat-
ing
Heating overload
Check refrigerant shortage/too much refrigerant
Expansion valve control
Ther-
mistor
Location
Wiring
symbol
Mode Function