EasyManua.ls Logo

Daikin Sky Air R-407C - Simulated Operation Function

Daikin Sky Air R-407C
304 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
ESIE02–01 General Functionality
Part 2 – Functional Description 2–15
3
2
4
5
1
1.10 Simulated Operation Function
Applicable units R(Y)P71-250B
RY35-45E(A)Z7V1
Purpose The purpose of the simulated operation function is to avoid the unit from stopping if the heat exchanger
thermistor or air thermistor is malfunctioning.
Method If the air thermistor (for all models listed) or the heat exchanger thermistor is malfunctioning (out of its
normal range), simulated operation is carried out while malfunction is displayed on the remote control.
If the air or heat exchanger thermistor becomes normal again, the simulated operation function is
interrupted and the normal operation restarts. The malfunctioning error disappears.
Used input The simulated operation function uses the following inputs:
Input
Connection on
indoor PCB
Connection on
outdoor PCB
Outdoor air thermistor R1T-X4A
Outdoor heat exchanger thermistor R2T-X5A
Indoor air thermistor R1T-X19A
Indoor heat exchanger thermistor R2T-X18A

Table of Contents

Related product manuals