ESIE02–01 Additional Checks for Troubleshooting
Part 3 – Troubleshooting 3–69
33
4
5
1
5.5 Outdoor unit: Checking the Installation Condition
Checking To check the installation condition, proceed as follows:
Check the space for all air
passage around the suction and
discharge areas.
Change the installation
location.
Does the
discharged air from other
outdoor units cause an
increase of the suction
temperature?
Is
the heat
exchanger
clean?
Is the
minimum space
respected?
Is there enough
air flow?
Clean the heat
exchanger.
Change the
installation
location or
direction.
Check the outdoor ambient
temperature R1T. This temperature
must be lower than 43 °C.
No
Yes
No
Yes
No
Yes
Change the installation
location.
Yes