ESIE02–01 Error Codes: Outdoor Units
Part 3 – Troubleshooting 3–43
33
4
5
1
3.5 Malfunctioning Electronic Expansion Valve (E9)
Error code E9
LED indications The table below shows the LED indications.
Error generation The error is generated when the following coil current condition is not met:
Open circuit < coil current < short circuit.
Resistance values The table below contains the reference resistance values.
Causes The possible causes are:
Malfunctioning electronic expansion valve
Broken or disconnected electronic expansion valve harness
Malfunctioning electronic expansion valve connector connection
Malfunctioning outdoor unit PCB
Outside cause (electric noise...).
Operation HAP (green) H1P (red) H2P (red)
Normal 688
Malfunction 688
Grey Black Yellow Red Orange
Grey
40-50 40-50 40-50 40-50
Black
40-50 80-100 80-100 80-100
Yellow
40-50 80-100 80-100 80-100
Red
40-50 80-100 80-100 80-100
Orange
40-50 80-100 80-100 80-100

Table of Contents