ESIE02–01 Specifications
Part 1 – System Outline 1–61
3
1
4
5
3.5 RY35 and RY45
Technical
specifications
The table below contains the technical specifications.
Electrical
specifications
The table below contains the electrical specifications.
Specification RY35EAZ7V1 RY45EAZ7V1
Compressor Model x No. 1YC43BTV1 1YC56ATV1N
Type Hermetically sealed swing type
Crankcase heater
Refrigerant oil type FVC68D + HAB15D
No. x motor output 1 x 1300 W 1 x 1700 W
Speed 2850 rpm 2860 rpm
No. of cylinders 1
Oil charge 850 cc
Heat exchanger Length 805 mm 788 mm
Rows x stages x fin pitch 1 x 24 x 2.0 mm 2 x 24 x 2.0 mm
No. of passes 1.67 3
Face area 0.513 m² 0.481 m²
Tube type Hi-XA
Fin type WL fin
Empty tubeplate hole 0
No. of fans 1
FanNominal air flow (230 V) cooling 36 m³/min 31 m³/min
Nominal air flow (230 V) heating 32 m³/min 28 m³/min
Fan motor model 19TFB6062
Nominal speed (230 V) H: 610 rpm
L: 350 rpm
Fan speed 2 steps
Refrigerant circuit Type R407C
Charge 1.1 kg 2.0 kg
No. of circuits Max. 1
Safety and functional devices See page 1–71
Heat insulation Both liquid and gas pipes
Weight 50 kg 57 kg
Specification RY35EAZ7V1 RY45EAZ7V1
Unit Phase 1~
Voltage 230 V
Frequency 50 Hz
No. of wire connections 3 for power supply (including earth wire)
4 for connecting with indoor (including earth wire)
Nominal running current (cool-
ing)
6.9 A 9.1 A
Nominal running current (heat-
ing)
6.4 A 8.8 A
Starting current (cooling) 34 A 42 A
Starting current (heating) 34 A 42A
Recommended fuses 16 A 20 A
Power supply intake Outdoor unit only
Fan motor No. of motors x output 1 x 30 W