2.6 Low Outside Temperature Control in Cooling Operation
(Year Round Cooling)
Applicable units R(Y)P71-250
Purpose The purpose of the control is to prevent freezing of the indoor heat exchanger due to:
Drop of the low pressure
Indoor heat exchanger temperature (Te).
Method The method to control is reduction of the air flow volume of the outdoor unit fan.
Starting and ending
conditions
The control is not activated during start-up control.
The control is activated when the outdoor temperature drops below (41.7 - 0.84 x room suction
temperature). At this temperature, the outdoor fan speed switches to L-tap.
The differential for the return condition is 4 K.
Outside air
temp. (Ta)
(˚CDB)
Indoor suction
air temp. (Tr)
(˚CDB)
L tap range
H tap range
Ta < 45.7 - 0.84 x Tr
Ta > 41.7 - 0.84 x Tr
(H tap return condition)
(L tap condition)
21 37
-5
46
24
28
11
15