ESIE02–01 Error Codes: Indoor Units
Part 3 – Troubleshooting 3–25
4
5
1
3
2.4 Indoor Unit Fan Motor Lock (A6)
Error code A6
LED indications The table below shows the LED indications.
Error generation The error is generated when the fan rotations are not detected while the output voltage to the fan is at
its maximum.
Causes The possible causes are:
Malfunctioning indoor unit fan motor
Broken or disconnected wire
Malfunctioning contact
Malfunctioning indoor unit PCB.