ESIE02–01 Error Codes: System Malfunctions
Part 3 – Troubleshooting 3–55
33
4
5
1
4.3 Reverse Phase (U1)
Error code U1
This error code is only for 3-phase equipment.
LED indication The table below shows the LED indication.
Error generation The error is generated when the difference between phase L1 and L3 is not 240˚. The illustration below
shows the 3-phase network.
Causes The possible causes are:
Malfunctioning power supply wiring connection
Broken or disconnected power supply wiring
Malfunctioning outdoor unit PCB
Operation HAP (green) H1P (red) H2P (red)
Normal 688
Malfunctioning 687
12090 180
L1 L2 L3
240
240˚
270 360
L1
L3 L2
240˚
120˚