EasyManua.ls Logo

Daikin Sky Air R-407C - Malfunctioning Drain Water Level System (A3)

Daikin Sky Air R-407C
304 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
ESIE02–01 Error Codes: Indoor Units
Part 3 – Troubleshooting 3–23
4
5
1
3
2.3 Malfunctioning Drain Water Level System (A3)
Error code A3
LED indications The table below shows the LED indications.
Error generation The error is generated when the water level reaches its upper limit and when the float switch turns
OFF.
Causes The possible causes are:
Malfunctioning drain pump
Improper drain piping work
Drain piping clogging
Malfunctioning float switch
Malfunctioning indoor unit PCB
Malfunctioning short-circuit connector X15 on PCB.
Operation HAP (green) HBP (green)
Normal 66
Malfunctioning 66

Table of Contents