EasyManua.ls Logo

Daikin Sky Air R-407C - Malfunctioning in Discharge Pipe Temperature (F3)

Daikin Sky Air R-407C
304 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
ESIE02–01 Error Codes: Outdoor Units
Part 3 – Troubleshooting 3–45
33
4
5
1
3.6 Malfunctioning in Discharge Pipe Temperature (F3)
Error code F3
LED indications The table below shows the LED indications.
Error generation The error is generated when:
Discharge pipe temperature becomes abnormally high
Discharge pipe temperature rises suddenly
Discharge pipe thermistor is not in its holder.
Causes The possible causes are:
Improper refrigerant amount
Clogging refrigerant piping circuit
Discharge temperature that is too low due to too much refrigerant or due to the discharge
thermistor being out of its holder
Discharge temperature that is too high.The possible causes are:
Operation HAP (green) H1P (red) H2P (red)
Normal 688
Malfunction 688
Excessively
high discharge
temperature
Refrigeration
shortage
Ÿ electrical fault coil
Ÿ mechanical fault body
Ÿ discharge thermistor
inaccuracy
insufficient suction
gas to
compressor
incorrect
operation of
expansion valve
caused by
caused by
caused by

Table of Contents