Field Setting from Remote Controller SiUS281811EA
166 Part 5 Field Settings and Test Operation
1.5.33 Room Temperature Display
For BRC1E series only
A "Detailed display screen" can be selected as the display screen. This setting is used if you do not
want "Room temperature display" to be shown on the "Detailed display screen".
: Factory setting
1.5.34 Thermistor Sensor for Auto Changeover and Setback Control by the
Remote Controller
For BRC1E series only
Select a thermistor to utilize for the cool/heat mode automatic changeover and setback functions.
The sensed temperature will be displayed on the remote controller as the room temperature.
: Factory setting
1.5.35 Access Permission Level Setting
For BRC1E series only
There are 2 levels as follows:
Level 2: The following buttons are selectable to be disable or enable.
Level 3: No buttons are selectable and only On/Off button is available.
( ) shows the factory setting
: Factory setting
Mode
No.
First Code
No.
Second Code
No.
Contents
1c 0
01 Room temperature is not displayed.
02
Room temperature is displayed.
Mode
No.
First Code
No.
Second Code
No.
Contents
1c 1
01 Utilize the return air thermistor
02
Utilize the remote controller thermistor
Button Level 2 Level 3
Selectable (Enable) Unselectable (Disable)
On/Off Selectable (Enable) Unselectable (Enable)
Mode Selectable (Enable) Unselectable (Disable)
Fan Speed Selectable (Enable) Unselectable (Disable)
Menu/OK Unselectable (Disable) Unselectable (Disable)
Cancel Unselectable (Disable) Unselectable (Disable)
Mode
No.
First Code
No.
Second Code
No.
Contents
1c 3
01
Level 2
02 Level 3