SiE-05C Wiring Adaptor
Appendix Inverter K Series / PLUS Series 385
<Settings of
Switches on The
PC Board Adaptor>
Note: For PLUS Series
Set the SS1 cool/heat selector switch on the function unit to outdoor. You must also set cool/heat selector
master or slave by pushbutton switch.
5.6.3 Demand / Low Noise Control
Connecting control input to the adaptor for outside control of outdoor units enables demand and low noise
control.
Demand Control
(Figures Indicate
Demand Rate)
When short circuit between (1) and (C): Approx. 70% as a guideline
When short circuit between (2) and (C): Approx. 40% as a guideline
When short circuit between (3) and (C): Forced fan operation
Low Noise Control
(Outdoor Unit)
Running noise can be reduced by 2~3dB by controlling capacity of outdoor unit.
<System Outline>