Installation and User Guide DEVIreg™ Multi
FEC | Produced by Danfoss ©42
Y14 #5 Manually On/Of Start or Stop control mode.
Caution: this mode may cause overheating and
damage!
0 1 0 – STOP Enum 6 RW 3093
H9 Channel #5 > Channel ON/OFF
Y15 #5 Channel ON/OFF If OFF – symbol # in the
line, algorithm is stopped, but real Temp. is
being shown
0 1 0 – OFF Enum 7 RW 3094
H11 Channel #5 > Sensor type
Y17 #5 Sensor type 0 7 1 – PT1000 Enum 9 RW 3095
H12 Channel #5 > Relay Status RO/RC
Y18 #5 Relay status - Set up Relay Opened (RO) or
Relay Closed (RC) for status ‘Heating On’
0 1 0 – RC Enum 10 RW 3096
H13 Channel #5 > Relay Test 5/30 sec.
Y19
#5 Relay Test 5/30 - Every 5 sec. switching for 30 sec.
0 1 0 – STOP Enum 6 RW 3097
Z1 Channel #6 > Regulation Type
T1 #6 Regulation Type: 1S – Single Sensor,
PR – Power Regulation
0 1 1 – 1S Enum 1 RW 3098
Z2 Channel #6 > Temp & Hysteresis
T2 #6 Set Temperature -50 200 5 °C RW 3099
T3 #6 Set +-Hysteresis 0.2 6 0.4 °C RW 3100
Z3 Channel #6 > On Time & Period
T4 #6 Set On Time 1 0 15 min. RW 3101
T5 #6 Set PR Period (max. 900 minutes) 0 900 30 min. RW 3102
Z4 Channel #6 > Alarm Temps & En/Dis
T6 #6 Alarm Temp En/Dis 0 1 0 – Dis Enum 5 RW 3103
T7 #6 Alarm min. Temp -50 0 0 °C RW 3104
T8 #6 Alarm max. Temp 0 200 60 °C RW 3105
Z5 Channel #6 > CableOK?
T9 #6 CableOK? En/Dis - Enable or Disable the
function of current monitoring in the load
0 1 0 – Dis Enum 5 RW 3106
T10 #6 CableOK? = NO/NC. Set up DI6 status
Normally Opened (NO) or Normally Closed (NC)
when cable is OK
0 1 1 – NO Enum 8 RW 3107
Z75 Power calculator > Channel Power #6
T11 #6 Channel Power (max. 32000) 0 32000 0 W RW 3108
Z8 Channel #6 > Manually On/Of
T12 #6 Manually On/Of Time – Set up period of time
for MOn or MOf status (max. 900 minutes)
1 900 1 min. RW 3109
T13 #6 Status On or Of for mode Heating Manually 0 1 0 – Of Enum 11 RW 3110
T14 #6 Manually On/Of Start or Stop control mode.
Caution: this mode may cause overheating and
damage!
0 1 0 – STOP Enum 6 RW 3111
Z9 Channel #6 > Channel ON/OFF
T15 #6 Channel ON/OFF If OFF – symbol # in the
line, algorithm is stopped, but real Temp. is
being shown
0 1 0 – OFF Enum 7 RW 3112