8 General Specifications and Troubleshooting
8.1 Mains Supply Specifications
8.1.1 Mains Supply 3x200-240 V AC
Frequency converter PK25 PK3
7
PK75 P1K
5
P2K2 P3K7 P5K5 P7K5 P11K P15K P18K P22K P30K P37K P45K
Typical shaft output [kW] 0.25 0.37 0.75 1.5 2.2 3.7 5.5 7.5 11.0 15.0 18.5 22.0 30.0 37.0 45.0
Typical shaft output [hp] 0.33 0.5 1.0 2.0 3.0 5.0 7.5 10.0 15.0 20.0 25.0 30.0 40.0 50.0 60.0
IP20 frame H1 H1 H1 H1 H2 H3 H4 H4 H5 H6 H6 H7 H7 H8 H8
Max. cable size in terminals
(mains, motor) [mm
2
/AWG]
4/10 4/10 4/10 4/10 4/10 4/10 16/6 16/6 16/6 35/2 35/2 50/1 50/1 95/0 120/
(4/0)
Output current
40 °C ambient temperature
Continuous
(3x200-240 V) [A]
1.5 2.2 4.2 6.8 9.6 15.2 22.0 28.0 42.0 59.4 74.8 88.0 115.0 143.0 170.0
Intermittent
(3x200-240 V) [A]
1.7 2.4 4.6 7.5 10.6 16.7 24.2 30.8 46.2 65.3 82.3 96.8 126.5 157.3 187.0
Max. input current
Continuous
3x200-240 V) [A]
1.1 1.6 2.8 5.6 8.6/
7.2
14.1/
12.0
21.0/
18.0
28.3/
24.0
41.0/
38.2
52.7 65.0 76.0 103.7 127.9 153.0
Intermittent
(3x200-240 V) [A]
1.2 1.8 3.1 6.2 9.5/
7.9
15.5/
13.2
23.1/
19.8
31.1/
26.4
45.1/
42.0
58.0 71.5 83.7 114.1 140.7 168.3
Max. mains fuses
See 5.2.3 Fuses and Circuit Breakers
Estimated power loss [W],
Best case/typical
1)
12/
14
15/
18
21/
26
48/
60
80/
102
97/
120
182/
204
229/
268
369/
386
512 697 879 1149 1390 1500
Weight enclosure IP20 [kg] 2. 2.0 2.0 2.1 3.4 4.5 7.9 7.9 9.5 24.5 24.5 36.0 36.0 51.0 51.0
Efficiency [%], best case/
typical
1)
97.0/
96.5
97.3/
96.8
98.0/
97.6
97.6/
97.0
97.1/
96.3
97.9/
97.4
97.3/
97.0
98.5/
97.1
97.2/
97.1
97.0 97.1 96.8 97.1 97.1 97.3
Output current
50 °C ambient temperature
Continuous
(3x200-240 V) [A]
1.5 1.9 3.5 6.8 9.6 13.0 19.8 23.0 33.0 41.6 52.4 61.6 80.5 100.1 119
Intermittent
(3x200-240 V) [A]
1.7 2.1 3.9 7.5 10.6 14.3 21.8 25.3 36.3 45.8 57.6 67.8 88.6 110.1 130.9
Table 8.1 3x200-240 V AC, PK25-P45K
1) At rated load conditions
General Specifications and ...
VLT
®
HVAC Basic Drive FC 101 Design Guide
98 MG18C502 - Rev. 2013-09-06
88

Table of Contents

Other manuals for Danfoss FC 101

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss FC 101 and is the answer not in the manual?

Danfoss FC 101 Specifications

General IconGeneral
ModelFC 101
ManufacturerDanfoss
Protection ClassIP20
Relative Humidity95% (non-condensing)
Communication InterfaceRS-485