5.2 Electrical Data
L1
L2
L3
3 Phase
power
input
PE
PE
+10 V DC
0-10 V DC-
0-10 V DC-
50 (+10 V OUT)
54 (A IN)
53 (A IN)
55 (COM A IN/OUT)
0/4-20 mA
0/4-20 mA
42 0/4-20 mA A OUT / DIG OUT
45 0/4-20 mA A OUT / DIG OUT
18 (DIGI IN)
19 (DIGI IN)
27 (DIGI IN)
29 (DIGI IN)
12 (+24 V OUT)
24 V (NPN)
20 (COM D IN)
O V (PNP)
24 V (NPN)
O V (PNP)
24 V (NPN)
O V (PNP)
24 V (NPN)
O V (PNP)
Bus ter.
Bus ter.
RS-485
Interface
RS-485
(N PS-485) 69
(P RS-485) 68
(Com RS-485 ) 61
(PNP)-Source
(NPN)-Sink
ON=Terminated
OFF=Unterminated
ON
1 2
240 V AC 3 A
Not present on all power sizes
Do not connect shield to 61
01
02
03
relay1
relay2
UDC+
UDC-
Motor
U
V
W
130BD467.10
06
05
04
240 V AC 3 A
Illustration 5.1 Basic Wiring Schematic Drawing
NOTICE
There is no access to UDC- and
UDC+ on the following units:
IP20 380-480 V 30-90 kW
IP20 200-240 V 15-45 kW
IP20 525-600 V 2.2-90 kW
IP54 380-480 V 22-90 kW
How to Install
VLT
®
HVAC Basic Drive FC 101 Design Guide
MG18C502 - Rev. 2013-09-06 53
5 5

Table of Contents

Other manuals for Danfoss FC 101

Related product manuals