5. Reconnect the mains supply - the frequency
converter is now reset.
Except the following parameters:
8-30 Protocol
8-31 Address
8-32 Baud Rate
8-33 Parity / Stop Bits
8-35 Minimum Response Delay
8-36 Maximum Response Delay
8-37 Maximum Inter-char delay
8-70 BACnet Device Instance
8-72 MS/TP Max Masters
8-73 MS/TP Max Info Frames
8-74 "I am" Service
8-75 Intialisation Password
15-00 Operating hours to 15-05 Over Volt's
15-03 Power Up's
15-04 Over Temp's
15-05 Over Volt's
15-30 Alarm Log: Error Code
15-4* Drive identification parameters
1-06 Clockwise Direction
2 finger initialisation
1. Power off the frequency converter.
2. Press [OK] and [Menu].
3. Power up the frequency converter while still
pressing the keys above for 10 s.
4. The frequency converter is now reset, except the
following parameters:
15-00 Operating hours
15-03 Power Up's
15-04 Over Temp's
15-05 Over Volt's
15-4* Drive identification parameters
Initialisation of parameters is confirmed by AL80 in the
display after the power cycle.
How to Programme
VLT
®
HVAC Basic Drive FC 101 Design Guide
MG18C502 - Rev. 2013-09-06 79
6 6

Table of Contents

Other manuals for Danfoss FC 101

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss FC 101 and is the answer not in the manual?

Danfoss FC 101 Specifications

General IconGeneral
ModelFC 101
ManufacturerDanfoss
Protection ClassIP20
Relative Humidity95% (non-condensing)
Communication InterfaceRS-485

Related product manuals