130BT312.10
Illustration 6.51 Insert Screwdriver
3. Insert the cable in the adjacent circular hole.
130BT311.10
Illustration 6.52 Insert Cable
4. Remove the screwdriver. The cable is now
mounted to the terminal.
130BT306.10
Illustration 6.53 Remove Screwdriver
To remove the cable from the terminal
1.
Insert a screwdriver
1)
in the square hole.
2. Pull out the cable.
1)
Max. 0.4 x 2.5 mm
6.5.6 Basic Wiring Example
1. Mount terminals from the accessory bag to the
front of the frequency converter.
2. Connect terminals 18 and 27 to +24 V (terminal
12/13)
Default settings
18 = Start, 5-10 Terminal 18 Digital Input [9]
27 = Stop inverse, 5-12 Terminal 27 Digital Input [6]
37 = Safe Torque Off inverse
12 13 18 37
130BA156.12
322719 29 33 20
P 5 - 12 [6]
P 5 - 10[9]
+24V
Speed
Start Stop inverse Safe Stop
Start (18)
Start (27)
Illustration 6.54 Basic Wiring
Electrical Installation Design Guide
MG11BC02 Danfoss A/S © Rev. 06/2014 All rights reserved. 111
6 6

Table of Contents

Other manuals for Danfoss FC 102