EasyManuals Logo
Home>Danfoss>DC Drives>FC 102

Danfoss FC 102 Design Guide

Danfoss FC 102
190 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #126 background imageLoading...
Page #126 background image
the present scan interval and no other events are
evaluated. This means that when the SLC starts, it
evaluates event [1] (and only event [1]) each scan interval.
Only when event [1] is evaluated TRUE, the SLC executes
action [1] and starts evaluating event [2].
It is possible to program from 0 to 20 events and actions.
When the last event/action has been executed, the
sequence starts over again from event [1]/action [1].
Illustration 7.4 shows an example with three events/actions:
130BA062.14
State 1
13-51.0
13-52.0
State 2
13-51.1
13-52.1
Start
event P13-01
State 3
13-51.2
13-52.2
State 4
13-51.3
13-52.3
Stop
event P13-02
Stop
event P13-02
Stop
event P13-02
Illustration 7.4 An Example with Three Events/Actions
7.1.7
SLC Application Example
2 sec
Max. ref.
P 3-03
2 sec
Preset ref.(0)
P 3-10(0)
State 1
State 3State 2
Preset ref.(1)
P 3-10(1)
Term 18
P 5-10(start)
130BA157.11
Illustration 7.5 One sequence 1: Start ramp up run at reference speed 2 sec ramp down and hold shaft until stop
Set the ramping times in 3-41 Ramp 1 Ramp Up Time and
3-42 Ramp 1 Ramp Down Time to the wanted times
t
ramp
=
t
acc
×
n
norm
par
. 1 25
ref
RPM
Set term 27 to No Operation (5-12 Terminal 27 Digital Input)
Set Preset reference 0 to first preset speed (3-10 Preset
Reference [0]) in percentage of Max reference speed
(3-03 Maximum Reference). Ex.: 60%
Set preset reference 1 to second preset speed (3-10 Preset
Reference [1] Ex.: 0 % (zero).
Set the timer 0 for constant running speed in 13-20 SL
Controller Timer [0]. Ex.: 2 sec.
Set Event 1 in 13-51 SL Controller Event [1] to True [1]
Set Event 2 in 13-51 SL Controller Event [2] to On Reference
[4]
Set Event 3 in 13-51 SL Controller Event [3] to Time Out 0
[30]
Set Event 4 in 13-51 SL Controller Event [4] to False [0]
Set Action 1 in 13-52 SL Controller Action [1] to Select preset
0 [10]
Set Action 2 in 13-52 SL Controller Action [2] to Start Timer
0 [29]
Set Action 3 in 13-52 SL Controller Action [3] to Select preset
1 [11]
Set Action 4 in 13-52 SL Controller Action [4] to No Action
[1]
Application Examples Design Guide
124 Danfoss A/S © Rev. 06/2014 All rights reserved. MG11BC02
77

Table of Contents

Other manuals for Danfoss FC 102

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss FC 102 and is the answer not in the manual?

Danfoss FC 102 Specifications

General IconGeneral
BrandDanfoss
ModelFC 102
CategoryDC Drives
LanguageEnglish

Related product manuals