80 | © Danfoss | August 2018 AQ00000211
Figure 38
When a successful spool calibration has been achieved, press “Accept and Save” button. PVED-CLS will now store the
values in the EEPROM for the following addresses:
Name
Description of parameter
Range
Max spool position, left P3162 S16 x10u Meter Spool left most position OEM, Dealer -1000 1000 -420
Max spool position,
right
P3164 S16 x10u Meter Spool right most position OEM, Dealer -1000 1000 420
Closed loop dead-band
edge, left
P3166 S16 x10u Meter Spool closed loop dead-band edge, Left OEM, Dealer -1000 1000 -105
Closed loop dead-band
edge, right
P3168 S16 x10u Meter Spool closed loop dead-band edge, Right OEM, Dealer -1000 1000 105
Open loop dead-band
edge offset
P3170 S16 x10u Meter Spool open loop dead-band offset OEM, Dealer -1000 1000 25
Table 34
Updating Valve Calibration Data sector manually and by auto-calibration function: