4.2.9 Summation Transformers
Multiple current sources
Summation CTs are needed when the filter is to
compensate current from several sources. This is often the
case if a filter is installed in systems with generator back-
up or where the filter is only to compensate a limited
number of loads, for example, marine installations.
M M
M
PCC1
130BB515.11
AAF
G
Illustration 4.11 Summation CTs on Generator Back-up
Applications (PCC-side)
M
M
M
AAF
PCC1
130BB516.11
Illustration 4.12 Summation CTs Example for Individual
Harmonic Compensation (Load Side)
Summation current transformers are available with
multiple (2–5) inputs and a common output. For
applications where summations CTs are used to add
current from several sources, make sure that all CTs
connected to the summation are from the same
manufacturer and that the following aspects are the same:
Polarity.
Primary rating.
RMS value.
Accuracy (class 0.5).
Location (PCC or load-side).
Phase sequence.
NOTICE
Use summation CTs with great caution and always
ensure correct phase sequence, current direction,
primary and secondary rating. Incorrect installation
causes problems with filter operation.
The current transformers burden calculation includes all
wires in the installation and must be conducted for the
longest total wire string when using summation CTs.
Electrical Installation
Operating Instructions
MG90V302 Danfoss A/S © 09/2014 All rights reserved. 23
4 4

Table of Contents

Other manuals for Danfoss VLT AAF006

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss VLT AAF006 and is the answer not in the manual?

Danfoss VLT AAF006 Specifications

General IconGeneral
BrandDanfoss
ModelVLT AAF006
CategoryWater Filtration Systems
LanguageEnglish